Product Structure
• Temperature range: -25~+105℃
• Rated voltage: U0/U 600V
• Test voltage: 2000V
• Insulation resistance: min. 10 MOhm x km
• Bending radius: fixed installation core Ø ≤ 8 mm: 4x core Ø; core Ø > 8-12 mm: 5x core Ø; core Ø > 12 mm: 6x core Ø
• Radiation resistance: up to 80x10⁶ cJ/kg (up to 80 Mrad)
Technical Data
• Temperature range: -25 to +105℃
\n• Rated voltage: U0/U 600V
\n• Test voltage: 2000V
\n• Insulation resistance: min. 10 MOhm x km
\n• Bending radius: Fixed installation core Ø ≤ 8 mm: 4x core Ø; core Ø > 8-12 mm: 5x core Ø; core Ø > 12 mm: 6x core Ø
\n• Radiation resistance: up to 80x10⁶ cJ/kg (up to 80 Mrad)
Product Features
· Good insulation and flame retardancy, prevents leakage due to short circuits or faults; good corrosion resistance, strong resistance to harsh natural environments; durable, protects the wire from external threats, thereby extending the service life of the wire.
· Self-extinguishing and flame retardant properties comply with DIN VDE 0482-332-1-2/DIN EN 60332-1-2/IEC 60332-1-2.
· Free of hazardous substances, compliant with ROHS standards.
Application Scope
• These single cores are suitable for laying in pipes, under plaster, on surfaces, and in closed installation conduits. Direct laying on cable trays, channels, or tanks is not permitted. They are permitted for internal wiring of equipment, distribution boards, and panels, as well as for protective laying of lighting equipment with a nominal voltage up to 1000V AC or up to 750V DC to ground.